The PL300 a PLC Data Acquisition Module which is designed to gather information and provide outputs for the ATR313, TD240, TD320 or other SCADA packages. The PL300 has four analog inputs which are selectable from K type thermocouple, T type thermocouple, J type thermocouple, R type thermocouple, S type thermocouple, E type thermocouple, Pt100, PT500, Ni100 and Ni1000 Resistance temperature detectors. The PL300 can also be programmed to accept universal input signals such as 4-20mA, 0-20mA, 0-1V and 0-10V. Along with the analog input the PL300 can also accept 6 PNP digital inputs.
The PL300 can have either 12 relay outputs or a combination of 4 solid state relays (SSR) with 8 relays. It also has 2 analog outputs either 0-10V or 4-20mA for retransmission or PID Control.
The PL300 is mountable on DIN rail. The PL300 has both RS232 and RS485 communication, a real time clock and can have a back up battery.
Input Analog | |
Thermocouple | K,S,T,R,J,E. |
Voltage | 0-20mV, 0-1 V, 0-10V |
Current | 0-20mA, 4-20mA |
RTD | PT100, NI100 |
Input Digital | 6 PNP, |
Output Analog | 0-10 V,4-20mA. |
Output Digital | 4 Solid State max 700mA 4Amp /group. |
Relay Digital | Up to 12 Relays 5 Amps. |
Power Supply | 12...24Vac/Vdc. |
Power Consumption | 10VA max. |
Temperature Range | Operative-32°F +113°F -0°C +45°C |
Humidity | (non condensing) 35-95%. |
Housing | DIN Rail |
Dimensions | 6.2" x 3.5" x 2.8",
160 x 90 x 58 mm |
Weight | 14 oz 460 g |
EMC | For industrial environments. |
Immunity: EN 61000-6-2. | |
Emission: EN 61000-6-4. | |
Configuration | PC Configurable, USB. |
Power Supply | ||
Positive 24Vdc | Terminal 1 | |
Negative | Terminal 2 | |
Analog Input | ||
Analog Input AI1+ | Terminal 22 | |
Analog Input AI1- | Terminal 23 | |
Analog Input AI1C | Terminal 24 | |
Analog Input AI2+ | Terminal 19 | |
Analog Input AI2- | Terminal 20 | |
Analog Input AI2C | Terminal 21 | |
Analog Input AI3+ | Terminal 15 | |
Analog Input AI3- | Terminal 16 | |
Analog Input AI3C | Terminal 12 | |
Analog Input AI4+ | Terminal 13 | |
Analog Input AI4- | Terminal 14 | |
Analog Input AI4C | Terminal 24 | |
Digital Inputs | ||
PNP 5 | Terminal 11 | |
PNP 6 | Terminal 10 | |
PNP 7 | Terminal 8 | |
PNP 8 | Terminal 7 | |
PNP 9 | Terminal 5 | |
PNP 10 | Terminal 3 | |
Common | Terminal 3, 6, 9, 18. | |
Output | PL300-10AD | PL300-30AD |
Relay 1 Common | Terminal 28 | |
Relay 1 NC | Terminal 29 | |
Relay 1 NO | Terminal 30 | |
Relay 2 Common | Terminal 31 | |
Relay 2 NC | Terminal 32 | |
Relay 2 NO | Terminal 33 | |
Relay 3 NO | Terminal 35 | |
Relay 4 NO | Terminal 36 | |
Relay 5 NO | Terminal 37 | Terminal 37 |
Relay 6 NO | Terminal 38 | Terminal 38 |
Relay 7 NO | Terminal 39 | Terminal 39 |
Common 3 to 7 | Terminal 34 | Terminal 34 |
Relay 8 NO | Terminal 41 | Terminal 41 |
Relay 9 NO | Terminal 42 | Terminal 42 |
Relay 10 NO | Terminal 43 | Terminal 43 |
Relay 11 NO | Terminal 44 | Terminal 44 |
Relay 12 NO | Terminal 45 | Terminal 45 |
Common 8 to 12 | Terminal 40 | Terminal 40 |
SSR1 | Terminal 30 | |
SSR2 | Terminal 29 | |
SSR3 | Terminal 33 | |
SSR4 | Terminal 32 | |
Positive signal for SSR | Terminal 35 and 36 | |
Output 13 | Terminal 50 | |
Output 14 | Terminal 51 | |
Output 15 | Terminal 52 | |
Output 16 | Terminal 53 | |
Common | Terminal 30 | |
Common | Terminal 54 | |
Analog output | PL300-10AD | PL300-30AD |
Output Positive 1 | Terminal 46 | Terminal 46 |
Output Negative 1 | Terminal 47 | Terminal 47 |
Output Positive 2 | Terminal 48 | Terminal 48 |
Output Negative 2 | Terminal 49 | Terminal 49 |