The Programmable Process Controller ATR621 is a panel mounted 73 x 73 mm multi cycle Process Controller. Each program can have up to 45 steps heating, cooling, and soaking. The ATR621 can store 15 different programs. It has digital input for door open interruptions, emergency or hold temperature function. The ATR621 has up to 3 relays, Voltage , current output as well as an option for Modbus RS485. The ATR621 accepts sensor inputs from K, J, S or R type thermocouples, Pt100 RTD's, Voltage and mA.
The ATR621 has two 4 digit displays, one for the process variable and the other for the set point.
The ATR621 is able to withstand environmental conditions up to IP54 with the optional gasket.
The ATR621 can be programmed with the front panel keypad or PC based software and multiple units can be cloned with the use of a memory card enabling high speed configuration. The PC based software can also be used to monitor several Temperature Controllers.
Desired control is maintained with PID and auto tuning.
Input | °F | °C |
K Type Thermocouple | -436 to 2480°F | -260 to 1360°C |
S Type Thermocouple | -40 to 3200°F | -40 to 1760°C |
R Type Thermocouple | -40 to 3200°F | -40 to 1760°C |
J Type Thermocouple | -328 to 1796°F | -200 to 980°C |
E Type Thermocouple | -328 to 1364°F | -436 to 740°C |
N Type Thermocouple | -328 to 2336°F | -260 to 1280°C |
RTD PT100 | -436 to 1112°F | -260 to 600°C |
Digital Input | 1 PNP. | |
Output: | ||
Relays | 3. 8 A 250V AC +1 Relay 5A 30V | |
Power Supply: | 24 to 230Vac/Vdc. | |
Power Consumption: | 5VA max. | |
Temperature rating: | Operative- 32°F +113°F -0°C +45°C | |
Humidity: | (non condensing) 35-95%. | |
Housing: | Polycarbonate UL94V2 self-extinguishing | |
Dimensions: | 2.83 " x 2.83 " x 3.89", 73 x 73 x 99 mm. | |
Weight: | 8.8 oz 250 g. | |
EMC. | For industrial environments. | |
Immunity:EN 61000-6-2. | ||
Emission: EN 61000-6-4. | ||
Configuration: | PC Configurable, Memory Card |
Power supply | ATR621-12ABC | ATR621-13ABC-T | ATR621-14ABC | |
Positive | Terminal 1 | Terminal 1 | Terminal 1 | |
Negative | Terminal 2 | Terminal 2 | Terminal 2 | |
Output | ||||
Relay 1 | ||||
Common | Terminal 4 | Terminal 4 | Terminal 4 | |
Normally Open | Terminal 3 | Terminal 3 | Terminal 3 | |
Normally Closed | Terminal 5 | Terminal 5 | Terminal 5 | |
Relay 2 | ||||
Common | Terminal 7 | Terminal 7 | Terminal 7 | |
Normally Open | Terminal 6 | Terminal 6 | Terminal 6 | |
Normally Closed | Terminal 8 | Terminal 8 | Terminal 8 | |
Relay 3 | ||||
Common | Terminal 7 | Terminal 7 | ||
Normally Open | Terminal 9 | Terminal 9 | ||
Relay 4 | ||||
Common | Terminal 10 | |||
Normally Open | Terminal 11 | |||
SSR Output | Negative 10 | Negative 10 | ||
Positive 11 | Positive 11 | |||
Sensor Input | ||||
Thermocouples | Positive 18 | Positive 18 | Positive 18 | |
Negative 17 | Negative 17 | Negative 17 | ||
Volts and mA | Positive 18 | Positive 18 | Positive 18 | |
Negative 17 | Negative 17 | Negative 17 | ||
RTD Pt100 | Terminal 17 | Terminal 17 | Terminal 17 | |
Common 16 | Common 16 | Common 16 | ||
Common 18 | Common 18 | Common 18 | ||
Digital input | Terminal 12 | Terminal 12 | ||
Terminal 13 | Terminal 13 | |||
RS485 | Positive 14 | |||
Negative 23 |
One Analog input, Two Relay Outputs 8 A 24 to 230 V ac/dc.
One Analog input, Modbus, Analog and Three Relay Outputs 8 A 24 to 230 V ac/dc.
One Analog input, Three Relay Outputs 8 A, One Relay 5 A, One digital input 24 to 230 V ac/dc.