The ATR444 Dual Controller is a single or dual controller with options for one or two analog inputs and outputs. Other main features are Modbus RTU and an array of optional Digital inputs, Relays, Solid State Relays, and current transformers inputs.
The ATR444 PID Controller has options for two loops controlling heating and cooling modes with separate control loop outputs. The screen is alphanumerical and is highly visible, and the keypad has eight keys that can be used to set up the controller and four function keys for use with other features and programmable functions.
The ATR444 has removable terminal blocks so the device can be replaced without the need to undo the wiring, and the terminal blocks are spring locking.
The ATR444 is programmed with the MYPixsys App with an NFC connection, or the LABSOFTVIEW software on a PC, or the front panel keyboard. It is straightforward to program with scrolling help and active alarm and status messages. You can set up the ATR444 without power connected to the device. The unit has indication of the process variable, the local or remote setpoint text indication, and a local bargraph.
The ATR444 has a high-speed analog to digital converter and has a response time of 252hZ 4 ms.
It has a highly efficient self-adapting tuning and is optimized to respond to process load variations. The ART444 has the option when both analog inputs are used to provide mathematical function such as averaging the two inputs, calculating the difference or the sum of the inputs. The inputs and outputs are galvanically isolated.
The ATR444 has the option of following a 12 step profile and can be used in combination with the 4 multi-purpose function keys.
Input | °F | °C |
K type Thermocouple | -436 to 2480°F | -260 to 1360°C |
S type Thermocouple | -40 to 3200°F | -20 to 1760°C |
R type Thermocouple | -40 to 3200°F | -20 to 1760°C |
J type Thermocouple | -328 to 2192°F | -200 to 1200°C |
T type Thermocouple | -436 to 752°F | -260 to 400°C |
E type Thermocouple | -436 to 1796°F | -260 to 980°C |
N type Thermocouple | -436 to 2336°F | -260 to 1280°C |
B type Thermocouple | 100 to 3308°F | 100 to 1820°C |
RTD PT100 | -328 to 1112°F | -200 to 600°C |
RTD PT500 | -328 to 284°F | -200 to 140°C |
NI 100 | -76 to 356°F | -60 to 180°C |
NI 120 | -76 to 464°F | -60 to 240°C |
NTC 10K Ohm Thermistor B3435K | -40 to 257°F | -40 to 125°C |
NTC 10K Ohm Thermistor B3694K | -40 to 302°F | -40 to 150°C |
NTC 2252 Thermistor B3976K | -40 to 302°F | -40 to 150°C |
PTC 1K Ohm Thermistor | -40 to 302°F | -40 to 150°C |
PT500 | -148 to 1112°F | -100 to 600°C |
PT1000 | -148 to 1112°F | -100 to 600°C |
Voltage | 0 to 1V | 0 to 5V |
Voltage | 0 to 10V | 0 to 60mV |
Current | 0 to 20mA | 4 to 20mA |
Potentiometer | 1 to 150 kOhm | |
Output | Upto 5 relays 5 Amp 250 VAC | 2 SSR 12/24, 25 mA |
Power Supply | 24 to 230Vac/Vdc. | |
Power Consumption | 8 to 12 W. | |
Power Supply | Operative- 32°F +113°F -0°C +45°C | |
Humidity | (non condensing) 35-95%. | |
Housing | Polycarbonate UL94V2 self-extinguishing | |
Dimensions | 1.88 " x 3.7869 " x 2.7", | 48 x 96 x 69 mm. |
Weight | 8.6 oz 245 g. | |
EMC | For industrial environments. | |
Immunity: EN 61000-6-2. | ||
Emission: EN 61000-6-4. | ||
Configuration | My Pixsys APP | PC Configurable |
Power Supply | ATR444-13ABC | ATR444-14ABC-T | ATR444-15ABC | ATR444-22ABC | ATR444-24ABC-T |
Positive | Terminal 1 | Terminal 1 | Terminal 1 | Terminal 1 | Terminal 1 |
Negative | Terminal 2 | Terminal 2 | Terminal 2 | Terminal 2 | Terminal 2 |
Output | |||||
Current and Voltage | |||||
Positive | Terminal 14 | Terminal 14 | Terminal 34 | Terminal 14 | |
Negative | Terminal 15 | Terminal 15 | Terminal 35 | Terminal 15 | |
Positive Channel 2 | Terminal 34 | ||||
Negative Channel 2 | Terminal 35 | ||||
Relay 1 | |||||
Normally Closed | Terminal 5 | Terminal 5 | Terminal 5 | Terminal 5 | Terminal 5 |
Common | Terminal 9 | Terminal 9 | Terminal 9 | Terminal 9 | Terminal 9 |
Normally Open | Terminal 4 | Terminal 4 | Terminal 4 | Terminal 4 | Terminal 4 |
Relay 2 | |||||
Normally Closed | Terminal 8 | Terminal 8 | Terminal 8 | Terminal 8 | Terminal 8 |
Common | Terminal 9 | Terminal 9 | Terminal 9 | Terminal 9 | Terminal 9 |
Normally Open | Terminal 7 | Terminal 7 | Terminal 7 | Terminal 7 | Terminal 7 |
Relay 3 | |||||
Common | Terminal 11 | Terminal 11 | Terminal 11 | Terminal 11 | |
Normally Open | Terminal 10 | Terminal 10 | Terminal 10 | Terminal 10 | |
Relay 4 | |||||
Common | Terminal 13 | Terminal 13 | Terminal 13 | ||
Normally Open | Terminal 12 | Terminal 12 | Terminal 12 | ||
Relay 5 | |||||
Common | Terminal 15 | ||||
Normally Open | Terminal 14 | ||||
Modbus RS485 | Negative 26 | Negative 28 | |||
Positive 25 | Positive 27 | ||||
SSR Output 1 | Negative 20 | Negative 20 | Negative 20 | Negative 20 | Negative 20 |
Positive 21 | Positive 21 | Positive 21 | Positive 21 | Positive 21 | |
SSR Output 2 | Negative 20 | Negative 20 | Negative 20 | Negative 20 | Negative 20 |
Positive 22 | Positive 22 | Positive 22 | Positive 22 | Positive 22 | |
Sensor Input 1 | |||||
Current | Positive 16 | Positive 16 | Positive 16 | Positive 16 | Positive 16 |
Negative 17 | Negative 17 | Negative 17 | Negative 17 | Negative 17 | |
Voltage | Positive 16 | Positive 16 | Positive 16 | Positive 16 | Positive 16 |
Negative 17 | Negative 17 | Negative 17 | Negative 17 | Negative 17 | |
Thermocouples | Positive 16 | Positive 16 | Positive 16 | Positive 16 | Positive 16 |
Negative 17 | Negative 17 | Negative 17 | Negative 17 | Negative 17 | |
Thermistor | Terminal 17 | Terminal 17 | Terminal 17 | Terminal 17 | Terminal 17 |
Terminal 18 | Terminal 18 | Terminal 18 | Terminal 18 | Terminal 18 | |
3 Wire RTD | Terminal 16 | Terminal 16 | Terminal 16 | Terminal 16 | Terminal 16 |
Terminal 18 | Terminal 18 | Terminal 18 | Terminal 18 | Terminal 18 | |
Wiper | Terminal 17 | Terminal 17 | Terminal 17 | Terminal 17 | Terminal 17 |
Potentiometer | Terminal 16 | Terminal 16 | Terminal 16 | Terminal 16 | Terminal 16 |
Terminal 18 | Terminal 18 | Terminal 18 | Terminal 18 | Terminal 18 | |
Wiper | Terminal 17 | Terminal 17 | Terminal 17 | Terminal 17 | Terminal 17 |
Sensor Input 2 | |||||
Current | Positive 29 | Positive 29 | |||
Negative 30 | Negative 30 | ||||
Voltage | Positive 29 | Positive 29 | |||
Negative 30 | Negative 30 | ||||
Thermocouples | Positive 29 | Positive 29 | |||
Negative 30 | Negative 30 | ||||
Thermistor | Terminal 30 | Terminal 30 | |||
Terminal 31 | Terminal 31 | ||||
3 Wire RTD | Terminal 29 | Terminal 29 | |||
Terminal 31 | Terminal 31 | ||||
Wiper | Terminal 30 | Terminal 30 | |||
Linear Potentiometer | Terminal 30 | Terminal 30 | |||
Terminal 31 | Terminal 31 | ||||
Digital Input DI1 | Terminal 20 | Terminal 20 | Terminal 20 | Terminal 20 | Terminal 20 |
Terminal 23 | Terminal 23 | Terminal 23 | Terminal 23 | Terminal 23 | |
Digital Input DI2 | Terminal 20 | Terminal 20 | Terminal 20 | Terminal 20 | Terminal 20 |
Terminal 24 | Terminal 24 | Terminal 24 | Terminal 24 | Terminal 24 | |
Digital Input DI3 | Terminal 20 | Terminal 20 | Terminal 20 | Terminal 20 | |
Terminal 24 | Terminal 24 | Terminal 24 | Terminal 24 | ||
Digital Input DI4 | Terminal 20 | Terminal 20 | Terminal 20 | Terminal 20 | |
Terminal 26 | Terminal 26 | Terminal 26 | Terminal 26 |